XHHW-2 COPPER CONDUCTOR

Cross-Linked Polyethylene Insulated 12 – 1000 MCM • 600/1000V • 90°C Dry and Wet

Description
Single conductor, 90℃ Wet/Dry. Insulated with chemically cross-linked polyethylene insulation.

Application
1000/600 Volt Type XHHW-2 is intended for use as general purpose wiring for up to 1000 volt rated services in air conduit or other recognized raceways for services, feeders and branch circuit wiring as specified in the National Electrical Code at a maximum conductor temperature of 90℃ in wet or dry locations.

Construction
● Conductors: Annealed stranded bare copper per ASTM B3 and B8. Class B Stranding per ASTM B8.
● Insulation: thermoset cross-linked polyethylene
● Colors: Available in black, white, red, blue, brown, orange, yellow, purple, gray, and green. Some colors are subject to economic order quantity.


Standards & References
Copper Type XHHW-2 conductors comply with the following:
● ASTM – B3 and B8
● Listed per UL Standard 44
● NEMA WC-70 (ICEA S-95-658) Construction Requirements
● Gas & Oil Resistant II – All Sizes
● CT Rated – Sizes 1/0 AWG and larger
● Wet/Dry Locations (90℃)
● Sunlight Resistant – Sizes 8 AWG and larger
● RoHS Compliant
 

Technical Parameter

ConductorInsulation thicknessNominal O.D.Approx. weightAmpacity
AWG/kcmilMin. No.mmmilsmmkg/km60℃75℃90℃
1270.76303.838202020
1070.76304.457303030
871.14455.794405055
671.14456.6142556575
471.14457.7218708595
271.14459.133685100115
1181.405510.442895115130
1/0181.405511.3533110130145
2/0181.405512.4664125150170
3/0181.405513.5830145175195
4/0181.405514.91036165200225
250351.656516.51237195230260
300351.656517.81470215255290
350351.656519.01704240285320
400351.656520.01946260310350
500351.656522.02410280335380
600582.038024.72916320380430
700582.038026.33390350420475
750582.038027.13622385460520
900582.038029.44328400475535
1000582.038031.04801455545615

+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and 240.4(D). Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
75℃ – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90℃ – THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.