TACSR/AW-Thermal-Resistant Aluminum Alloy Conductor Aluminum Clad Steel Reinforced

Thermal-Resistant Aluminum alloy conductor ,aluminum clad steel reinforced is a high ampacity conductor with inner core composed of Aluminum clad Steel & outer layer composed of thermal resistant aluminium alloy with round.

Application
Thermal-Resistant Aluminum alloy conductor aluminum clad steel reinforced is used for overhead transmission line, ground line, electric railway. Due to its obvious advantage of anti-corrosion and high strength, it is applicable for long- span line, severe cold zone with heavy snow and other bad weather besides general transmission line.Used for power plant, power transmission and distribution line, the voltage ranges from 1 kV to 750 kV, especially used in compacity – expansion route and transformation of the old lines.

Description 
Thermal-Resistant Aluminum alloy conductor ,aluminum clad steel reinforced is a high ampacity conductor with inner core composed of Aluminum clad Steel & outer layer composed of thermal resistant aluminium alloy with round.

Specification
● IEC 61089 Round Wire Concentric Lay Overhead Electrical Stranded Conductors 
● IEC 62004 Thermal -Resistant Aluminum Alloy Wires For Overhead Line Conductor 
● NB/T 42060 Thermal -Resistant Aluminum Alloy Conductors, Steel Core Reinforced For Overhead Transmission Line

Technical Parameter

JNRLH1 / LB20A

Nominal AreaNo. of WiresDiameterAreaDiameterLinear
Mass
Rated StrengthDC. Resistance at 20℃
TALStTALStTALStTotalJNRLH1/
LB20A
mm²No.mmmm²mmkg/kmkNΩ/km
300/402473.992.66300.138.9339.023.91085.594.390.0936
300/502673.832.98299.548.8348.324.31150.3106.20.0928
400/354873.222.5390.934.4425.326.81307.6104.60.0729
400/505473.073.07399.751.8451.527.61448.6126.90.0704
400/652674.423.44398.965.1464.028.01532.2140.20.0697
500/354573.762.51499.734.6534.330.11609.9122.50.0574
500/454873.62.8488.643.1531.730.01635.5130.90.0584
630/454574.222.81629.443.4672.833.82026.5152.20.0456
630/554874.123.2639.956.3696.234.32141169.30.0446
720/504574.533.02725.350.1775.436.22336175.50.0396
800/554574.83.2814.356.3870.638.42622.7197.00.0352

Note:
Conductivity of TAL: 60% IACS       Continuous operating temperature of conductor :150℃
Aluminium Clad Steel :20.3% IACS

JNRLH1 / LB14
Nominal AreaNo. of WiresDiameterAreaDiameterLinear
Mass
Rated StrengthDC. Resistance at 20℃
TALStTALStTALStTotalJNRLH1/
LB14
mm²No.mmmm²mmkg/kmkNΩ/km
300/402473.992.66300.138.933923.91106.9102.60.0948
300/502673.832.98299.548.8348.324.31177.2116.50.0944
400/354873.222.5390.934.4425.326.81326.6111.80.0736
400/505473.073.07399.751.8451.527.61477.2136.30.0714
400/652674.423.44398.965.1464281568.1153.20.0708
500/354573.762.51499.734.6534.330.11629.1129.80.0578
500/454873.62.8488.643.1531.7301659.3139.90.0589
630/454574.222.81629.443.4672.833.82050.5161.30.0459
630/554874.123.2639.956.3696.234.32172.1179.40.045
720/504574.533.02725.350.1775.436.22363.7184.50.0398
800/554574.83.2814.356.3870.638.42653.8207.20.0355


Note:
Conductivity of TAL: 60% IACS       Continuous operating temperature of conductor :150℃
Aluminium Clad Steel :14% IACS

TACSR/AW

Nominal AreaNo. of WiresDiameterAreaDiameterLinear
Mass
Rated StrengthDC. Resistance at 20℃
TALStTALStTALStTotal
mm²No.mmmm²mmkg/kmkNΩ/km
1603072.62.615937.2196.218.2068668.40.171
2403073.23.224156.3297.322.40102499.50.112
3302674.03.132752.8379.825.301252107.20.085
4102674.53.541467.3481.328.501569136.10.0671
5205473.53.552067.3587.331.501881153.00.0567
6105473.83.861279.4691.434.202219180.00.0458
6804574.42.968446.2730.235.102201152.90.0421
8104574.83.281456.3870.338.402627180.90.0353
11608474.24.2116497.01261.046.203873273.80.0246
15208474.84.81520126.71646.752.805058357.80.0190


Note:
Conductivity of TAL: 60% IACS       Continuous operating temperature of conductor :150℃