38 kV to 66 kV-(72.5 kV) – CU/XLPE/LEAD/HDPE
HV cable is used for the transmission and distribution of electric power and is suitable for installation in ducts, trenches or direct buried underground or within buildings. These cables are ideal for use to connect wind farms and other renewable energy to existing grid systems.
Construction
- Conductor: stranded circular or segmantal compacted copper or aluminium
- Conductor screen: semi-conducting layer
- Insulation: XLPE
- Insulation screen: non metallic – semi-conducting layer
- Tape: non-conductive water blocking
- Sheath: lead
- Outer sheath: HDPE sheathed with graphite coating or extruded semi-conducting layer (LSZH available on request)
- Standard colour: black
- Marking: ELECTRIC CABLE 38/66kV + Gongniu Cable type Cable Size(e .g . “1×150”) COMMODITY CODE IEC 60840+ lot production + year + metre marking
Standards
Technical Parameter
38/66 kV Corrugated Aluminum Sheath Cable Parameters
Nominal Area | Alu. sheath thickness (Minimum) | Outer sheath thickness (Nominal) | Overall Diameter (Approx.) | App. Weight (Aluminium) | App. Weight (Copper) | Approx. Capacitance |
mm2 | mm | mm | mm | kg/m | kg/m | μF/km |
95 | 1.8 | 2.4 | 51 | 4.4 | 5.3 | 0.15 |
120 | 1.8 | 2.5 | 53 | 4.8 | 5.9 | 0.16 |
150 | 1.8 | 2.6 | 55 | 5.2 | 6.5 | 0.16 |
185 | 1.8 | 2.6 | 57 | 5.7 | 7.3 | 0.18 |
240 | 1.9 | 2.7 | 60 | 6.5 | 8.5 | 0.19 |
300 | 1.9 | 2.8 | 62 | 7.2 | 9.2 | 0.2 |
400 | 2 | 3 | 66 | 8.1 | 10.4 | 0.22 |
500 | 2.1 | 3 | 69 | 8.9 | 11.9 | 0.24 |
630 | 2.2 | 3.1 | 73 | 9.9 | 13.6 | 0.26 |
800 | 2.3 | 3.3 | 78 | 11 | 15.9 | 0.29 |
1000 | 2.4 | 3.4 | 81 | 12.2 | 18.2 | 0.31 |