RHH/RHW-2/USE-2 ALUMINUM CONDUCTOR

Cross-Linked Polyethylene Insulated 6 – 1000 MCM • 600V • 90°C Dry and Wet • Direct Burial

Application
Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the National Electrical Code. When used as Type USE-2, conductors are suitable for use as underground service entrance conductors for direct burial at conductor temperatures not to exceed 90°C. When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHW-2 or RHH or USE-2 conductors is 600 volts.

Construction
Type RHH or RHW-2 or USE-2 conductors are AA-8000 series aluminum alloy, compact stranded. The insulation is an abrasion, moisture, heat and sunlight-resistant black cross-linked polyethylene (XLP). CT rated available upon request sizes 1/0 and larger.

Features
● Conductor for reduced diameter
● General purpose use in construction:
● Residential
● Commercial
● Institutional
● Industrial construction

Standards & References
Type RHH or RHW-2 or USE-2 conductors comply with the following:
● ASTM B-800 and B-801
● UL 44 for RHH or RHW-2
● UL 854 for USE-2
● National Electrical Code, NFPA 70, 2011 Edition
● NEMA WC-70 Construction Requirements
● RoHS/Reach Compliant
 
 

Technical Parameter

ConductorInsulation thicknessNominal O.D.Approx. weightAmpacity+
AWG/kcmilMin. No.mmmilsmmkg/km60℃75℃90℃
671.52607.367405060
471.52608.595556575
271.52609.91367590100
1182.038011.718585100115
1/0182.038012.6222100120135
2/0182.038013.6267115135150
3/0182.038014.8324130155175
4/0182.038016.1394150180205
250352.419518.0480170205230
300352.419519.3560190230255
350352.419520.5639210250280
400352.419521.6719225270305
500352.419523.5874260310350
600582.7911026.21065285340385
700582.7911027.91221310375420
750582.7911028.61297320385435
900582.7911031.01529355425480
1000582.7911032.51685375445500


+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and 240.4(D)

Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
75℃ – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90℃ – THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.