XHHW-2 ALUMINUM CONDUCTOR
Description
Single conductor, 90℃ Wet/Dry. Insulated with chemically cross-linked polyethylene insulation.
Application
1000/600 Volt Type XHHW-2 is intended for use as general purpose wiring for up to 1000 volt rated services in air conduit or other recognized raceways for services, feeders and branch circuit wiring as specified in the National Electrical Code at a maximum conductor temperature of 90℃ in wet or dry locations.
Construction
● Conductors: AA-8000 series aluminum alloy, compact stranded.
● Insulation: thermoset cross-linked polyethylene
● Colors: Available in black, white, red, blue, brown, orange, yellow, purple, gray, and green. Some colors are subject to economic order quantity.
Standards & References
Aluminum Type XHHW-2 conductors comply with the following:
● ASTM – B800 and either B801 or B836 (SIW)
● Listed per UL Standard 44
● NEMA WC-70 (ICEA S-95-658) Construction Requirements
● Gas & Oil Resistant II – All Sizes
● CT Rated – Sizes 1/0 AWG and larger
● Wet/Dry Locations (90℃)
● Sunlight Resistant – Sizes 6 AWG and larger
● RoHS Compliant
Technical Parameter
Conductor | Insulation thickness | Nominal O.D. | Approx. weight | Ampacity + | ||||
AWG/kcmil | Min. No. | mm | mils | mm | kg/km | 60℃ | 75℃ | 90℃ |
8 | 7 | 1.14 | 45 | 5.7 | 41 | 35 | 40 | 45 |
6 | 7 | 1.14 | 45 | 6.6 | 58 | 40 | 50 | 55 |
4 | 7 | 1.14 | 45 | 7.7 | 84 | 55 | 65 | 75 |
2 | 7 | 1.14 | 45 | 9.1 | 124 | 75 | 90 | 100 |
1 | 18 | 1.40 | 55 | 10.4 | 160 | 85 | 100 | 115 |
1/0 | 18 | 1.40 | 55 | 11.3 | 196 | 100 | 120 | 135 |
2/0 | 18 | 1.40 | 55 | 12.4 | 239 | 115 | 135 | 150 |
3/0 | 18 | 1.40 | 55 | 13.5 | 293 | 130 | 155 | 175 |
4/0 | 18 | 1.40 | 55 | 14.9 | 360 | 150 | 180 | 205 |
250 | 35 | 1.65 | 65 | 16.5 | 435 | 170 | 205 | 230 |
300 | 35 | 1.65 | 65 | 17.8 | 511 | 195 | 230 | 260 |
350 | 35 | 1.65 | 65 | 19.0 | 587 | 210 | 250 | 280 |
400 | 35 | 1.65 | 65 | 20.0 | 665 | 225 | 270 | 305 |
500 | 35 | 1.65 | 65 | 22.0 | 814 | 260 | 310 | 350 |
600 | 58 | 2.03 | 80 | 24.7 | 998 | 285 | 340 | 385 |
700 | 58 | 2.03 | 80 | 26.3 | 1150 | 315 | 375 | 425 |
750 | 58 | 2.03 | 80 | 27.1 | 1224 | 320 | 385 | 435 |
900 | 58 | 2.03 | 80 | 29.4 | 1450 | 355 | 425 | 480 |
1000 | 58 | 2.03 | 80 | 31.0 | 1601 | 375 | 445 | 500 |
+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and 240.4(D). Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
75℃ – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90℃ – THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.
YOU MAY LIKE
Related products
-
Building Wire
H05VV-F (RVV)
-
Building Wire
XHHW-2 COPPER CONDUCTOR
-
Building Wire
RHH/RHW-2/USE-2 COPPER CONDUCTOR
-
Building Wire
RHH/RHW-2/USE-2 ALUMINUM CONDUCTOR
-
Building Wire
THWN or THHN
-
Building Wire
H07V-U – BV (Cu/PVC)
-
Building Wire
H07V-R (BVR)
-
Building Wire
H07V-K (RV)