H07V-K (RV)

Application 
Insulated conductor is used for laying in electric – installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment.

Construction
● Conductor: Copper, class 1, solid conductors 
● Insulation: Polyvinyl chloride PVC

Specification
IEC 60228 Conductors of Insulated Cables
IEC 60227-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring
DIN VED 0281-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including 450/750 V – Part 3: Non-sheathed Cables for Fixed Wiring
Note: We also can produce based on other international standards etc.
Characteristics
● Rated voltage Uo/U: 450/750 V;
● Normal operating temperature: 70˚C.
● Short circuit temperature (5 seconds maximum duration): 160˚C.
● IEC 60227-3 (mark 60227 IEC 01)
● Minimum bending radius:
   4D for D < 8mm
   5D for 8mm < D < 12mm
   6D for D > 12mm
Note: D is overall diameter of cable.

Technical Parameter

ConductorInsulation ThicknessOverall DiameterApprox. WeightMax. D.C. Resistance of Conductor
at 20℃
Allowable Ampacities
  Min.Max.   
mm²Class of
Conductor
mmmmmmkg/kmΩ/kmA
1.550.72.83.42113.318
2.550.83.44.1347.9825
450.83.94.8504.9533
650.84.45.3713.3042
1051.05.76.81071.9158
1651.06.78.11691.2178
2551.28.410.22660.780105
3551.29.711.73470.554130
5051.411.513.94860.386155
7051.413.216.07050.272200
9551.615.118.29050.206250
12051.616.720.211170.161290
15051.818.622.513800.129335
18552.020.624.917420.106390
24052.223.528.421520.0801470